NOAA Targets Hurricanes With Computer Power

A new NOAA supercomputing facility in West Virginia could help improve weather forecasters' ability to predict the power of huge hurricanes, which could eventually help public officials make better decisions about evacuations.

Data Center Knowledge

September 19, 2011

3 Min Read
ITPro Today logo in a gray background | ITPro Today

DarrenSmith

Darren Smith, the NESCC Project Director for NOAA, is overseeing the completion of a new data center in West Virginia that will house the agency's next-generation supercomputer.

A new supercomputing facility in West Virginia could help improve weather forecasters' ability to predict the power of huge hurricanes, which could eventually help public officials make better decisions about when to call for the kind of mass evacuations seen during Hurricane Irene.

Next month The National Oceanographic and Atmospheric Administration (NOAA) will bring a new data center online. The facility in Fairmont, West Virginia will support a 383-teraflop supercomputer designed to develop more powerful tools for analyzing the behavior of hurricanes. NOAA staffers discussed the project in a presentation last week at the AFCOM Data Center World fall conference in Orlando.

Computer Models Improving

Hurricane scientists have developed sophisticated computer models to analyze the threat posed by hurricanes. This has helped forecasters make significant strides in projecting the path a hurricane will take. But it remains more difficult to predict the intensity of hurricanes, which can fluctuate in strength as they approach landfall. Hurricane intensity is ranked on the Saffir-Simpson scale, which assigns a category from 1 to 5, with Category 5 storms being the most powerful.

"The damage caused by the hurricane has almost everything to do with intensity," said NOAA's Darren Smith, who said predicting the intensity requires granular data."The physics of a hurricane occur at a 1 kilometer resolution."

The new supercomputer in West Virginia will bring more horsepower to test new models designed to better measure intensity. But it will also require about five years of development before the new model is ready for use in NOAA forecasts.

More Capacity Required

Analyzing hurricane data requires lots of computing power. NOAA has 9 supercomputers already, but none of its existing facilities had the space or power capacity to house the new machine. Smith and his team began an unusual site selection process in which they picked a location for the new facility without knowing what kind of supercomputer it would house.

They didn't know, for example, whether the supercomputer would require water cooling or air cooling. The agency eventually chose an SGI Altix ICE cluster in which some cabinets will be water-cooled (through a rear-door cooling unit) while others will use air cooling.

Cabinets in the high performance computing cluster will use up to 33 kilowatts of power per rack. The data center will use full outside air cooling (air economization) for 40 percent of the year, while using a mix of economizers and chillers the remainder of the time. The economizers are expected to save about $800,000 a year in power costs.

The 54,000 square foot space will house 16,000 square feet of computer room space on a 4-foot raised floor, and a 6,000 square foot tape archive, with room for expansion of both. The facility has 6 megawatts of power capacity, and is supported by a flywheel UPS system.

Thermal Storage for Ride-Through Cooling

The NOAA facility is supported by a 32-foot tall thermal storage tank, which holds 25,000 gallons of water chilled at 55 degrees. At full load, the thermal storage will provide about 10 minutes of cooling in the event of a power outage to allow time to restart the chillers.

Smith said the growth of the NOAA supercomputing program is part of a larger effort to offer more granular information at a time when instance of severe weather are on the rise.

"We need climate modeling down to local environments," said Smith. "The public is demanding a lot more service from NOAA."

Read more about:

Data Center Knowledge

About the Author

Data Center Knowledge

Data Center Knowledge, a sister site to ITPro Today, is a leading online source of daily news and analysis about the data center industry. Areas of coverage include power and cooling technology, processor and server architecture, networks, storage, the colocation industry, data center company stocks, cloud, the modern hyper-scale data center space, edge computing, infrastructure for machine learning, and virtual and augmented reality. Each month, hundreds of thousands of data center professionals (C-level, business, IT and facilities decision-makers) turn to DCK to help them develop data center strategies and/or design, build and manage world-class data centers. These buyers and decision-makers rely on DCK as a trusted source of breaking news and expertise on these specialized facilities.