Vancouver Power Outage KOs Plenty of Fish update from July 2008

An underground circuit fire caused a major power outage in Vancouver, resulting in a generator failure at the Harbour Centre telecom hub.

2 Min Read
ITPro Today logo in a gray background | ITPro Today

An underground circuit fire caused a major power outage in Vancouver yesterday, which disabled traffic lights and cash machines and also led to lengthy outages for web sites hosted at the Harbour Centre telecom hub. The main generator supporting the Harbour Centre failed, cutting power to a data center operated by Peer 1.

Among the sites affected by the five-hour outage were Plenty of Fish, the massively popular free dating site operated by Internet entrepreneur Markus Frind. Plenty of Fish is known for supporting huge web traffic on a lightweight infrastructure, as well as Frind's ability to generate revenue using Google AdSense. Other sites affected by the outage included the web host services Bravenet and Blue Fur.


Peer 1 kept customers informed via its forums, and President and CEO Fabio Banducci posted a post-mortem and timeline shortly after service was restored, in which he explained the generator issue:

Harbour Centre's main building generator, Gen No.7, started and maintained power as designed, but failed 20 minutes after the loss of commercial power due to a failure in the generator's cooling system. Gen No.7's cooling system is dependent upon water provided by the city of Vancouver and requires a certain level of water pressure to function normally. As fire fighters worked to put out the fire that had broken out on Richards Street, water pressure in the downtown core, (including Harbour Center), declined to a point where it caused the generator to overheat and malfunction. Once the generator failed, PEER 1's UPS systems eventually failed as well once the UPS batteries had drained.

Harbour Centre was able to get the generator working by 3:40 pm local time, and Peer 1 restored power to customers by 4:20 pm. At 5:55 pm the building was back on utility power. Banducci emphasized that Peer 1 would fully honor its customer service level agreements (SLAs) and take steps to avoid a repeat of the outage.

Harbour Centre is a 28-floor skyscraper in the central business district of downtown Vancouver, which also serves as the city's primary telecom and data center hub. The building's description of its telecommunications infrastructure states that the property has six diesel generators ranging from 250 kilowatts to 1.5 megawatts in capacity.

Read more about:

Data Center Knowledge

About the Author

Data Center Knowledge

Data Center Knowledge, a sister site to ITPro Today, is a leading online source of daily news and analysis about the data center industry. Areas of coverage include power and cooling technology, processor and server architecture, networks, storage, the colocation industry, data center company stocks, cloud, the modern hyper-scale data center space, edge computing, infrastructure for machine learning, and virtual and augmented reality. Each month, hundreds of thousands of data center professionals (C-level, business, IT and facilities decision-makers) turn to DCK to help them develop data center strategies and/or design, build and manage world-class data centers. These buyers and decision-makers rely on DCK as a trusted source of breaking news and expertise on these specialized facilities.